Worksheet GL-a2
by M. Fraganza and M. Miccio based on the Examination test of January 28, 2016
rev. 1.1 of 03.04.2019


Objective

  • Selection and sizing of a globe control valve using the inherent characteristic data provided by the manufacturer in the form of a table.

Go


to data input

Data provided by the manufacturer

Fisher PF51.2:HP globe valve - Intrinsic linear characteristic

Valve opening

Valve size

(inches)

NB: The intrinsic characteristic is actually LINEAR only in the central section

Data provided by the manufacturer

Fisher PF51.2:HP globe valve - Equal percentage intrinsic characteristic

Valve opening

Valve size

(inches)

NB: The actual intrinsic characteristic is not exactly exponential

Data input for the liquid:


NB:

The data pre-entered in the fields are those of the examination problem of January 28, 2016

Select the liquid

specific density

atm
Pa
psi
bar

Input upstream pressure P1

Input downstream pressure P2

input vapor pressure Pv

kg/s
lb/min

input mass flow rate

Data input for the valve:


input the nominal diameter (inch) of the valve

linear
equalpercentage

Select the intrinsic characteristic

Verification of the choice by comparing the Cv to 70% of the stroke

Nominal diameter (inch) chosen for the valve:

"

Application of the 70% rule to the chosen valve:

◄══►